RJ3XX series high-precision power analyzer is divided into RJ311/310/330/340/360, corresponding to 1 channel, 3 channel, 4 channel and 6 channel, the performance indicators of each channel are the same, multi-channel under the control of the main control CPU, can be combined operation, such as to achieve three-phase measurement, input and output efficiency measurement. The series of power analyzer has high precision, fast sampling, and many functions. In addition to the basic electrical parameter measurement function, there are harmonic analysis function, integration function, ratio function, data storage/call out function, communication function, etc., which can be applied to the enterprise quality inspection, R & D department and third-party testing department with high precision requirements.

Product introduction Main Features Technical Specifications Download

RJ3XX series high-precision power analyzer is divided into RJ311/310/330/340/360, corresponding to 1 channel, 3 channel, 4 channel and 6 channel, the performance indicators of each channel are the same, multi-channel under the control of the main control CPU, can be combined operation, such as to achieve three-phase measurement, input and output efficiency measurement. The series of power analyzer has high precision, fast sampling, and many functions. In addition to the basic electrical parameter measurement function, there are harmonic analysis function, integration function, ratio function, data storage/call out function, communication function, etc., which can be applied to the enterprise quality inspection, R & D department and third-party testing department with high precision requirements.       


Input signal bandwidth: DC, 0.5Hz ~ 100kHz digital tube display;

Sampling frequency: 100kS/s;

Basic accuracy: ± (0.05%rdg.+0.1%f.s.);

Current measurement: 2A/5A/20A/50A optional;

With voltage, current harmonic analysis function;

Can display waveform and trend chart;

Measurement data and screenshot pictures can realize U disk storage.


Model selection

Model number

Channel

Display mode

RJ311

1

7 pieces of nixie tube

RJ310

1

5.6 "LCD display

RJ330

3

RJ340

4

RJ360

6

 


Model number

RJ311

RJ310

RJ330

RJ340

RJ360

Input signal bandwidth

DC, 0.5Hz  ~  100 kHz

Basic accuracy

± (0.05%×rdg.+0.1%×f.s.)

DC, 0.5Hz to 100 kHz

DC, 0.5Hz to 100 kHz

DC, 0.1Hz to 1MHz

 

 

Sampling frequency

100 kS/s

100 kS/s

100 kS/s

100 kS/s

100 kS/s

Measuring channel

1

1

1, 2, 3

1 to 4

1 to 6

Measuring the range

Voltage (V)

15/30/60/100/150/300/600/1000 [V]

Current (A) :

Direct input

2 A card:        5m/10m/20m/50m/0.1/0.2/0.5/1/2 [A]

5 A card:        10m/20m/50m/0.1/0.2/0.5/1/2/5 [A]

20A card:        0.5/1/2/5/10/20 [A]

20 A [W] card:    5m/10m/20m/50m/0.1/0.2/0.5/1/2/5/10/20 [A]

50A card:        1/2/5/10/20/50[A]

 

 

 

 

 

 

Power (W)

2A calorie:       0.1mW440W@220VPF=0.011

5A card:         0.2mW1.1kW@220VPF=0.011

20A card:        1.1mW4.4kW@220VPF=0.011

20A[W] card:     0.1mW4.4kW@220VPF=0.011

50A card:        22mW11kW@220VPF=0.011

Measurement accuracy

Voltage measurement accuracy

DC                ±(0.1%rdg.+0.1%f.s.)

0.5Hz≤f45Hz      ±(0.1%rdg.+0.2%f.s.)

45Hz≤f≤66Hz       ±(0.1%rdg.+0.1%f.s.)

66Hzf≤1kHz      ±(0.1%rdg.+0.2%f.s.)

1kHzf≤10kHz     ±({0.1+0.05×(f-1)}%rdg.+0.2%f.s.)

10kHzf≤100kHz   ±({0.5+0.04×(f-10)}%rdg.+0.3%f.s.)

Accuracy of current measurement

DC                ±(0.1%rdg.+0.1%f.s.)

0.5Hz≤f45Hz      ±(0.1%rdg.+0.2%f.s.)

45Hz≤f≤66Hz       ±(0.1%rdg.+0.1%f.s.)

66Hzf≤1kHz      ±(0.1%rdg.+0.2%f.s.)

1kHzf≤10kHz     ±((0.1×f)%rdg.+0.2%f.s.)

10kHzf≤100kHz   ±({1+0.08×(f-10)}%rdg.+0.3%f.s.)

Accuracy of power measurement

DC                ±(0.1%rdg.+0.1%f.s.)

0.5Hz≤f45Hz      ±(0.3%rdg.+0.2%f.s.)

45Hz≤f≤66Hz       ±(0.1%rdg.+0.1%f.s.)

66Hzf≤1kHz      ±(0.2%rdg.+0.2%f.s.)

1kHzf≤10kHz     ±({0.2+0.1×(f-1)}%rdg.+0.2%f.s.)

10kHzf≤50kHz    ±({0.2+0.1×(f-1)}%rdg.+0.3%f.s.)

50kHzf≤100kHz   ±({5.1+0.18×(f-50)}%rdg.+0.3%f.s.)

Measuring function

Harmonic analysis

is

is

is

is

is

Waveform display

no

is

is

is

is

Custom range jump

is

is

is

is

is

Line frequency filtering

OFF, 500Hz, 5.5kHz

 

is

is

is

 

 

Measuring parameters

Main measurement parameters

Voltage RMS Urms, DC voltage Udc, AC voltage Uac, current RMS Irms, DC current Idc, AC current Iac, active power P, reactive power Q, apparent power S, power factor PF, phase Angle φ, voltage frequency fU, current frequency fI, positive and negative peak voltage U+pk/ U-PK, positive and negative peak current I+ pk/I-pk, voltage peak factor CfU, current peak factor CfI, electric energy WP, current integral q, integral time, average active power AVP, average current AVI

Simultaneous measurement

RMS/DC/AC

 

is

is

is

is

is

Show

Display screen

4 rows LED nixie tube

Highlight display

5.6-inch color LCD display

Display Format

Numerical value

Numerical values, waveforms, trends, bar charts

Data update cycle

100m/200m/500m/1/2/5[S]

Other indicators

Interfaces

RS232(standard), RS485/USB/GP-IB/LAN(optional)

Removable memory

USB

USB

USB

USB

Use environment

0℃ ~ 40℃,20%RH ~ 70%RH

Power supply

AC220V, 50/60Hz

Weight

3kg

3kg

5kg

6kg

8kg

Exterior size

(W×H×D)

mm

213×88×420 without foot, foot height 15mm

340×133×505

without foot, foot height 15mm

432×133×505 

without foot, foot height 15mm


Customer site