Model | RJ311 | RJ310 | RJ330 | RJ340 | RJ360 |
Input Signal Bandwidth | DC,0.5Hz~100kHz |
Basic Accuracy | ±(0.05%rdg.+0.1%f.s.) |
Sampling frequency | 100kS/s |
Measuring channel | 1 |
| 1,2,3 | 1~4 | 1~6 |
Measurement range | Voltage(V) | 15/30/60/100/150/300/600/1000[V] |
Current (A). Direct Input | 2A card: 5m/10m/20m/50m/0.1/0.2/0.5/1/2[A] 5A card: 10m/20m/50m/0.1/0.2/0.5/1/2/5[A] 20A card 5m/50m/0.5/5/20[A] 50A card 0.5/5/20/50[A] |
Power (W) | 2A card: 5A card: 20A card: 20A [W] card: 50A card: | 0.1mW~440W@220V,PF=0.01~1 0.2mW~1.1kW@220V,PF=0.01~1 1.1mW~4.4kW@220V,PF=0.01~1 0.1mW~4.4kW@220V,PF=0.01~1 22mW~11kW@220V,PF=0.01~1 |
Measurement Accuracy | Voltage Measurement Accuracy | DC 0.5Hz≤f<45Hz 45Hz≤f≤66Hz 66Hz<f≤1kHz 1kHz<f≤10kHz 10kHz<f≤100kHz | ±(0.1%rdg.+0.1%f.s.) ±(0.1%rdg.+0.2%f.s.) ±(0.1%rdg.+0.1%f.s.) ±(0.1%rdg.+0.2%f.s.) ±({0.1+0.05×(f-1)}%rdg.+0.2%f.s.) ±({0.5+0.04×(f-10)}%rdg.+0.3%f.s.) |
Current Measurement Accuracy | DC 0.5Hz≤f<45Hz 45Hz≤f≤66Hz 66Hz<f≤1kHz 1kHz<f≤10kHz 10kHz<f≤100kHz | ±(0.1%rdg.+0.1%f.s.) ±(0.1%rdg.+0.2%f.s.) ±(0.1%rdg.+0.1%f.s.) ±(0.1%rdg.+0.2%f.s.) ±((0.1×f)%rdg.+0.2%f.s.) ±({1+0.08×(f-10)}%rdg.+0.3%f.s.) |
Power Measurement Accuracy | DC 0.5Hz≤f<45Hz 45Hz≤f≤66Hz 66Hz<f≤1kHz 1kHz<f≤10kHz 10kHz<f≤50kHz 50kHz<f≤100kHz | ±(0.1%rdg.+0.1%f.s.) ±(0.3%rdg.+0.2%f.s.) ±(0.1%rdg.+0.1%f.s.) ±(0.2%rdg.+0.2%f.s.) ±({0.2+0.1×(f-1)}%rdg.+0.2%f.s.) ±({0.2+0.1×(f-1)}%rdg.+0.3%f.s.) ±({5.1+0.18×(f-50)}%rdg.+0.3%f.s.) |
Measurement Functions | Harmonic analysis | Yes | Yes | Yes | Yes | Yes |
Waveform display | No | Yes | Yes | Yes | Yes |
Customized range jumping | Yes | Yes | Yes | Yes | Yes |
Line frequency filtering | OFF, 500Hz, 5.5kHz |
Measurement Parameters | Main Measurement Parameters | RMS voltage Urms, DC voltage Udc, AC voltage Uac, RMS current Irms, DC current Idc, AC current lac, active power P, reactive power Q, apparent power S, power factor PF, phase angle φ, voltage frequency fU, current frequency f1, positive and negative peak voltages U+pk/U-pk, positive and negative peak currents I+pk/l-pk, peak voltage factor CfU, peak current factor Cfl, electrical energy WP, current integral q, integration time, average active power AVP, average current AVI |
Simultaneous measurement of RMS/DC/AC | C is | Yes | Yes | Yes | Yes |
Display | Display screen | 4-line LED digital tube; high brightness display | 5.6-inch color LCD screen |
Display Format | Numeric | Numerical, waveform, trend, bar graph |
Data update cycle | 100m/200m/500m/1/2/5[S] |
Other indicators | Interface | RS232 (standard), RS485/USB/GP-IB/LAN (optional) |
Removable Memory | USB |
Operating Environment | 0℃~40℃,20%RH~70%RH |
Power Supply | AC220V,50/60Hz |
Weight | 3kg | 3kg | 5kg | 6kg | 11.8kg |
External Dimension (W×H×D)mm | 213×88×420 without feet Height of feet 15mm | 340×133×505 excluding under-chassis, with under-chassis height of 15mm | 432×133×505 Lower quality machine with under-chassis height of 15mm |
Accompanying documents and Accessories | 1 instruction manual, 1 power cord (1.5 meters), 1 communication cable (1.5 meters) |